Runtime/Load
All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
The ION F15 UPS is the latest Pure Sine Wave Line Interactive UPS featuring automatic voltage regulation (AVR). With its compact form factor, the F15 UPS can be utilized as a standalone tower or under a computer monitor with all sizes from 500VA to 1500VA. The Larger 1kVA and 1.5kVA have the option to be rack mounted if required.
The F15 is the affordable way for homes or businesses to flexibly integrate reliable power supply and protect switches, servers, networking devices, security and point-of-sale equipment.
FEATURES
ION F15 comes in four models 500VA, 750VA, 1000VA and 1500VA
High frequency design pure sine wave output delivers superior DC-AC
- Efficiency
- Microprocessor control
- Cold Start function allows restart without AC power input
- Energy saving green power option
- Autostart in AC recovery
- Modem phone line power surge protection
- Discharge Overcharge and Overload protection
- Autocharge when UPS is switched off
- Easy user replaceable batteries
- USB interface with software communications port
- Optional rack kit for 1000VA and 1500VA models
PERFECT FOR
- Office Computer Server Rooms
- Commercial IT
- Retail POS
- IP Telephony
- Security Applications
- Short Depth Rack Mount Solutions
PROTECTION FOR
- Servers
- Switches
- Routers
- Networking devices
- Storage Devices
| 500VA | 750VA | 1000VA | 1500VA | |
| Capacity | ||||
| VA / W | 500VA/300W | 750VA/500W | 1000VA/600W | 1500VA/870W |
| Input | ||||
| Voltage | Variable 220 – 240VAC | |||
| Normal Frequency | 50Hz | |||
| Output | ||||
| Voltage | Variable 220 – 240VAC | |||
| Regulation (Normal Mode) | (+/-15% Max) of normal voltage | |||
| Regulation (Battery Mode) | (+/-10%) | (+/-5%) | ||
| Voltage Waveform | Pure Sine Wave | |||
| Frequency | 50Hz | |||
| Overload Capacity | ||||
| Normal Mode | (110% +8%), fault after 3 minutes: (130% +8%), fault after 10 cycles minimum | |||
| Boost/Buck Mode | (70% +8%/-4%): overload alarming after 25 minutes, fault after 30 minutes | |||
| Battery Mode | 110% ±8%, fault after 30 seconds; 120% ±8%, fault after 5 cycles minimum | |||
| Connections | ||||
| Inlet | IEC C14 (1) | |||
| Outlets | IEC C13 (4) | IEC C13 (4) | IEC C13 (6) | IEC C13 (6) |
| Transfer Time | ||||
| Typical | 2-7 ms typical, 10ms max | |||
| Efficiency | ||||
| Normal Mode | > 95% (Rated full load, battery full charged) | |||
| Boost/Buck Mode | > 90% (Rated full load, battery full charged) | |||
| Battery Mode | > 80% (Rated full load, battery full charged) | |||
| Back Up Time | ||||
| 50% load Backup Time (Typical) | 12 min | 8 min | 11 min | 10 min |
| 100% load Backup Time (Typical) | 6 min | 4 min | 6 min | 5 min |
| User Interface | ||||
| LED Display | UPS Status / Load Level / Battery Level / Fault | |||
| Audible Alarm | Yes | |||
| Dimensions | ||||
| W x D x H (mm) | 96 x 300 x 236 | 86 x 390 x 328 | ||
| Weight | ||||
| Weight | 5.6 kg | 6 kg | 9.8 kg | 10.2 kg |
| Environment | ||||
| Operating Temperature | 0 – 40 °C | |||
| Relative Humidity | 0 to 90% Relative Humidity (Non-condensing) | |||
| Audible noise at 1 meter | <40 dBA | <45 dBA | ||
| Conformance | ||||
| Approvals | CE | |||
| Standard warranty | 3 Year Advance Replacement* | |||