Unity Power Factor

Pure Sine Wave

LCD Display

Optional SNMP

3 Year Replacement Warranty

2RU

WiFi
Runtime/Load
All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
The ION F18-IOT Rack/Tower delivers unity output power factory. High density, true double conversion on-line power protection for IT (Information technology) and OT (operation technology) applications. Capable of supporting loads from 1 to 20kVA in a rack/tower convertible form with a 2U/3U space. These range of UPS comes with future-proof connectivity design having the capability to connect to cloud seamlessly to allow the monitoring of the UPS online through internet connected device.
FEATURES
- Capability to connect to cloud
- 3 year advanced replacement warranty*
- Maintenance bypass module optional
- Unity 1.0 power factor
- Wide voltage input range
- High efficiency
- Optional additional batteries for extendable run time
- Automatic detect numbers of EBM
- Digital charger; charging current 0-4A adjustable
- Dual input
- Power management software
- Multiple communication ports
- Optional SNMP and relay cards
- Optional Wi-Fi communication module*
- 1+1 Parallel capacity up to 3
- Smallest footprint in its class
PERFECT FOR
- Commercial Data Centres
- Manufacturing Systems
- Medical equipment
- Industrial applications
- Telecom – VoIP
- Industrial Equipment
PROTECTION FOR
- High end servers
- Switches, Servers, Routers
- Networking and wireless devices
- PLC systems
- Security systems
- Data storage systems
F18-IOT-1kW-RT |
F18-IOT-1.5kW-RT |
F18-IOT-2kW-RT |
F18-IOT-3kW-RT |
F18-IOT-6kW-RT |
F18-IOT-10kW-RT | |
Output |
||||||
Output power capacity |
1000Watts / 1000VA | 1500Watts / 1500VA | 2000Watts / 2000VA | 3000Watts / 3000VA | 6000Watts / 6000VA | 10000Watts / 10000VA |
Max Configurable Power (Watts) |
1000Watts / 1000VA | 1500Watts / 1500VA | 2000Watts / 2000VA | 3000Watts / 3000VA | 6000Watts / 6000VA | 10000Watts / 10000VA |
Nominal Output Voltage |
200/208/220/230/240 VAC (derating 10% at 208V, derating 20% at 200V) |
220 / 230 / 240VAC | ||||
Voltage Accuracy |
±1% |
|||||
Frequency |
50Hz/60Hz |
|||||
Topology |
Double Conversion Online |
|||||
Waveform type |
Pure Sine Wave |
|||||
Output Connections |
IEC C13 (8) |
IEC C13 (8) |
IEC C13 (8) |
IEC C13 (8) IEC C19 (1) |
L/N/PE hardware terminal connection |
|
Bypass |
Internal Bypass (Automatic and Manual) |
|||||
Input |
||||||
Nominal Input Voltage |
230V |
220 / 230 / 240VAC | ||||
Input frequency Range |
50/60 Hz +/- 3 Hz (auto sensing) |
|||||
Input Connections |
IEC-320 C14 |
IEC-320 C14 |
IEC-320 C14 |
IEC-320 C20 |
L/N/PE hardware terminal connection |
|
Input voltage range for main operations |
160-300V 100% load, 110-160V derating to 50% load linearly |
160-275V 100% load 110-160V derating to 50% load linearly |
||||
Overload Capacity |
||||||
Line Mode |
100%<load≤105% continuous. |
100%<load≤105% continuous. 105%< load ≤125% for 10 minutes 125<load≤150% for 30 seconds. >150% for 500ms. |
||||
Efficiency |
||||||
Double Conversion Mode |
89% |
93% |
95% |
|||
ECO Mode |
96% |
97% |
98% |
|||
UPS Batteries |
||||||
Battery type |
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
|||||
Number of Batteries/Battery Rating |
NA |
|||||
Expected Battery Life (years) |
3-5 years |
|||||
Extendable Run Time |
Yes |
|||||
Battery Replacement | Hot Swappable | Replacement EBM | ||||
Charging Current | 2A/ 4A/ 6A/ 8A (adjustable) | 4A (2-12A adjustable) | ||||
Recharging Time | NA | |||||
Communications & Management |
||||||
Interface Port(s) |
RS232 / USB / EPO |
|||||
Communications Card Slot |
Optional SNMP / AS400 Card / MODBUS Card |
|||||
Control panel |
Load / Battery / Input / Output / Operating Mode Information |
|||||
Audible Alarm |
Yes |
|||||
UPS Dimensions |
F18-IOT-1kW-RT |
F18-IOT-1.5kW-RT |
F18-IOT-2kW-RT |
F18-IOT-3kW-RT |
F18-IOT-6kW-RT |
F18-IOT-10kW-RT |
RU |
2 |
|||||
Maximum Height |
85.5mm |
86.3mm |
||||
Maximum Width |
438mm |
|||||
Maximum Depth |
445mm |
600mm |
573mm |
|||
Net Weight |
8.0kg |
8.2kg |
10.6kg |
11.0kg |
13.6kg |
15.5kg |
IP Protection Level | IP20 | |||||
EBM Dimensions |
F18-IOT-EBM-36V-RT |
F18-IOT-EBM-36V-RT |
F18-IOT-EBM-72V-RT |
F18-IOT-EBM-72V-RT |
F18-IOT-EBM-240V-RT |
F18-IOT-EBM-240V-RT |
Numbers of Batteries / Battery Rating |
2 x 3 x 12V 7AH |
2 x 6 x 12V 9AH |
20 x 12V 9AH |
|||
Maximum connect external battery module quantity |
8 | 16 | ||||
External battery module auto detection | Yes | Yes | ||||
RU | 2 | 3 | ||||
Maximum Height |
85.5mm |
129mm |
||||
Maximum Width |
438mm |
438mm |
||||
Maximum Depth |
445mm |
600mm |
593mm |
|||
Net Weight |
19.8kg |
22.6kg |
39.9kg |
39.9kg |
60.5kg |
|
Environmental |
||||||
Operating Environment |
0 – 40 °C |
0-50°C (power derating to 50% @40-50°C ) | ||||
Operating Relative Humidity |
0 – 95 % |
|||||
Operating Elevation |
0-3000meters |
|||||
Storage Temperature |
-15 – 45 °C |
|||||
Storage Relative Humidity |
0 – 95 % |
|||||
Storage Elevation |
0-15000meters |
|||||
Audible noise at 1 meter from surface of unit |
<45dB @ typical load with battery fully charged |
<50dB @ typical load with battery fully charged |
<55dB @ typical load with battery fully charged | |||
Conformance |
||||||
Approvals |
CE,IEC/EN 62040 |
|||||
Standard warranty |
3 Year Advanced Replacement* |