Product Overview
Specifications
Downloads
The ION Online Double Conversion outdoor UPS has been designed for protecting outdoor communication and networking equipment. Being able to resist the elements from high temperature, cold environments, salt spray resistance, corrosive environments, dust prevention, water resistance and provides lighting protection. The FHT also has a wide range of input voltage and frequency providing a stable output and have been designed around applications for outdoor communication base stations for communication, radio, television and more.
FEATURES
- 12 Month warranty*
- IP55 protection, dust prevention and waterproof, perfectly fit in harsh environment
- Lightning protection, equipped with no less than 1.2KV/10KA pluggable SPD
- Wide voltage input range
- High/low temperature resistance design, sun shading, heat insulation and temperature compensation designs, operating normally at -20 “C – +45 “C
- Long run time applications
- Wide input voltage range (110 Vac ~ 300 Vac) and frequency range (45 Hz ~ 65 Hz) make it fully adapt to harsh power grid environment
- Optional SNMP & relay cards
PERFECT FOR
- Outdoor applications
- Mining
- Harsh environments from hot, cold temperature
- Salt spray resistant and corrosive environments
- Dust and water resistance
- Communication based stations
- Industrial applications
- Telecom – VoIP
- Industrial Equipment
PROTECTION FOR
- High end servers
- Switches, Servers, Routers
- Networking and wireless devices
- PLC systems
- Security systems
- Data storage
FHT-1000 | FHT-2000 | FHT-3000 | |
Output | |||
Output Power Capacity | 800Watts / 1000VA | 1600Watts / 2000VA | 2400Watts / 3000VA |
Max Configurable Power | 800Watts / 1000VA | 1600Watts / 2000VA | 2400Watts / 3000VA |
Output phase | Single-phase three-wire (1 Ø +N+PE) | ||
Rated voltage | 208V / 220 V / 230 V / 240 Vac (Programmable) | ||
Voltage regulation accuracy | ± 2% | ||
Frequency accuracy | Synchronized with utility in mains mode, 50 / 60 Hz ± 0.1 Hz in battery mode | ||
Power factor | 0.8 | ||
Waveform distortion | < 2% (resistive load); < 5% (non-linear load) | ||
Crest factor | 3:01 | ||
Inverter overload capability | 108% <load < 150% for 30 s, load> 150% for 200 ms | ||
Input | |||
Input phase | Single-phase three-wire (1 Ø +N+PE) | ||
Rated voltage | 208 V / 220 V / 230 V / 240 Vac | ||
Input voltage range | 110 Vac – 140 Vac (half load), 140 Vac – 300 Vac (full load) | ||
Input frequency range | 45 – 55 Hz (rated on 50 Hz)/ 55 – 65 Hz (rated on 60 Hz) | ||
Power factor | > 0.99 | ||
Bypass input voltage range | Minimum bypass voltage range = rated voltage – 34 V / Maximum bypass voltage range = rated voltage + 32 V | ||
Battery voltage | 24 Vdc | 48 Vdc | 72 Vdc |
Inbuilt battery space | 2 x 12 V / 65 – 100 AH | 4 x 12 V / 65 – 100 AH | 6 x 12 V / 65 – 100 AH |
System | |||
Efficiency | > 90% | ||
Transfer time | Mains mode <——-> Bypass mode: < 4 ms / Mains mode< > Battery mode: O ms | ||
Protections | Output short circuit, output overload, overtemperature, battery low voltage, output overvoltage / undervoltage, fans fault | ||
Communication interfaces | Standard configuration: RS232 and dry contacts, Optional configuration: SNMP card, RS485, temperature compensation | ||
Power distribution units | Mains/ battery input/ output circuit breaker, input/ output terminal, output sockets, maintenance bypass switch, SPD | ||
Display | LED | ||
Environmental | |||
Operating temperature | -20°C – 45°C | ||
Storage temperature | -45°C – 70°C (without batteries) | ||
Relative humidity | 0% – 95% (non-condensing) | ||
Altitude | < 1000 m, > 1000 m (derating 1% for each additional 100 m) | ||
IP rating | IP 55 | ||
Noise | < 50 dB (at 1 m) | ||
UPS Dimensions | FHT-1000 | FHT-2000 | FHT-3000 |
Dimensions W x D x H (mm) | 600 X 334 X 990 | 600 X 434 X 1110 | |
Color | White |